変圧制御マイクログリッドにおける変動電圧ダイナミクスに対する性能指標
Performance metrics for droop-controlled microgrids with variable voltage dynamics
Performance metrics for droop-controlled microgrids with variable voltage dynamics
@misc{tegling2016performance,
title = {Performance metrics for droop-controlled microgrids with variable voltage dynamics},
author = {Emma Tegling and Dennice F. Gayme and Henrik Sandberg},
year = {2016},
eprint = {1601.08023},
archivePrefix = {arXiv},
primaryClass = {math.OC},
url = {https://arxiv.org/abs/1601.08023}
}
Tegling, E., Gayme, D. F., & Sandberg, H. (2016). Performance metrics for droop-controlled microgrids with variable voltage dynamics [Preprint]. arXiv. https://doi.org/10.48550/arXiv.1601.08023
TEGLING E, GAYME DF, SANDBERG H. Performance metrics for droop-controlled microgrids with variable voltage dynamics[EB/OL]. (2016-01-29)[2026-11-29]. https://arxiv.org/abs/1601.08023.
要旨
本論文は、持続的な微小擾乱下、同期維持のために発生する総電力損失の観点から、ドロップ制御インバーターを備えたマイクログリッドの性能を調査する。インバーターはドロップ制御下で可変周波数と電圧を持つモデル化される。定常状態からの微小変動に対して、これらの遷移電力損失は、分布擾乱にさらされる線形システムの入力出力 H2 ノルムによって定量化される。本 H2 ノルムは、主に誘導性ネットワークかつ同様のインバーターを持つ仮定の下で評価される。結果は、従来の知見に従い位相同期が損失をネットワークサイズに比例してスケールさせるものの、接続性への依存は弱い一方で、電圧制御に関連する損失は、疎なネットワークに比べて高接続性のネットワークでより大きくなることを示している。したがって、高接続性のネットワークにおける通常より高い収束速度は、定常状態に到達するために使用される電力流に関連する高い損失の代償を伴う。
This paper investigates the performance of a microgrid with droop-controlled inverters in terms of the total power losses incurred in maintaining synchrony under persistent small disturbances. The inverters are modeled with variable frequencies and voltages under droop control. For small fluctuations from a steady state, these transient power losses can be quantified by an input-output H2 norm of a linear system subject to distributed disturbances. We evaluate this H2 norm under the assumption of a dominantly inductive network with identical inverters. The results indicate that while phase synchronization, in accordance with previous findings, produces losses that scale with a network's size but only weakly depend on its connectivity, the losses associated with the voltage control will be larger in a highly connected network than in a loosely connected one. The typically higher rate of convergence in a highly interconnected network thus comes at a cost of higher losses associated with the power flows used to reach the steady state.