Voltage Estimation in Low-Voltage Distribution Grids with Distributed Energy Resources
@misc{markovi2020voltage,
title = {Voltage Estimation in Low-Voltage Distribution Grids with Distributed Energy Resources},
author = {Marija Marković and Amirhossein Sajadi and Anthony Florita and Robert Cruickshank III and Bri-Mathias Hodge},
year = {2020},
eprint = {2011.05598},
archivePrefix = {arXiv},
primaryClass = {eess.SY},
url = {https://arxiv.org/abs/2011.05598}
}
Marković, M., Sajadi, A., Florita, A., III, R. C., & Hodge, B.-M. (2020). Voltage Estimation in Low-Voltage Distribution Grids with Distributed Energy Resources [Preprint]. arXiv. https://doi.org/10.48550/arXiv.2011.05598
MARKOVIĆ M, SAJADI A, FLORITA A, et al. Voltage Estimation in Low-Voltage Distribution Grids with Distributed Energy Resources[EB/OL]. (2020-11-11)[2026-11-29]. https://arxiv.org/abs/2011.05598.
Abstract
The present distribution grids generally have limited sensing capabilities and are therefore characterized by low observability. Improved observability is a prerequisite for increasing the hosting capacity of distributed energy resources such as solar photovoltaics (PV) in distribution grids. In this context, this paper presents learning-aided low-voltage estimation using untapped but readily available and widely distributed sensors from cable television (CATV) networks. The CATV sensors offer timely local voltage magnitude sensing with 5-minute resolution and can provide an order of magnitude more data on the state of a distribution system than currently deployed utility sensors. The proposed solution incorporates voltage readings from neighboring CATV sensors, taking into account spatio-temporal aspects of the observations, and estimates single-phase voltage magnitudes at all non-monitored buses using random forest. The effectiveness of the proposed approach was demonstrated using a 1572-bus feeder from the SMART-DS data set for two case studies - passive distribution feeder (without PV) and active distribution feeder (with PV). The analysis was conducted on simulated data, and the results show voltage estimates with a high degree of accuracy, even at extremely low percentages of observable nodes.